- Source: High-leg delta
High-leg delta (also known as wild-leg, stinger leg, bastard leg, high-leg, orange-leg, red-leg, dog-leg delta) is a type of electrical service connection for three-phase electric power installations. It is used when both single and three-phase power is desired to be supplied from a three phase transformer (or transformer bank). The three-phase power is connected in the delta configuration, and the center point of one phase is grounded. This creates both a split-phase single-phase supply (L1 or L2 to neutral on diagram at right) and three-phase (L1–L2–L3 at right). It is sometimes called orange leg because the L3 wire is required to be color-coded orange in the United States. By convention, the high leg is usually set in the center (B phase) lug in the involved panel, regardless of the L1–L2–L3 designation at the transformer.
Supply
High-leg delta service is supplied in one of two ways. One is by a three-phase transformer (or three single-phase transformers), having four wires coming out of the secondary, the three phases, plus a neutral connected as a center-tap on one of the windings. Another method (the open delta configuration) requires two transformers. One transformer is connected to one phase of the overhead primary distribution circuit to provide the lighting side of the circuit (this will be the larger of the two transformers), and a second transformer is connected to another phase on the circuit and its secondary is connected to one side of the lighting transformer secondary, and the other side of this transformer is brought out as the high leg. The voltages between the three phases are the same in magnitude, however the voltage magnitudes between a particular phase and the neutral vary. The phase-to-neutral voltage of two of the phases will be half of the phase-to-phase voltage. The remaining phase-to-neutral voltage will be √3/2 the phase-to-phase voltage. So if A–B, B–C and C–A are all 240 volts, then A–N and C–N will both be 120 volts, but B–N will be 208 volts.
Other types of three-phase supplies are wye connections, ungrounded delta connections, or corner-grounded delta (ghost leg configuration) connections. These connections do not supply split single-phase power, and do not have a high leg.
Explanation
Consider the low-voltage side of a 120/240 V high leg delta connected transformer, where the b phase is the high leg. The line-to-line voltage magnitudes are all the same:
V
a
b
=
V
b
c
=
V
c
a
=
240
V
.
{\displaystyle V_{ab}=V_{bc}=V_{ca}=240\,{\text{V}}.}
Because the winding between the a and c phases is center-tapped, the line-to-neutral voltages for these phases are as follows:
V
a
n
=
V
c
n
=
V
a
c
2
=
120
V
.
{\displaystyle V_{an}=V_{cn}={\frac {V_{ac}}{2}}=120\,{\text{V}}.}
But the phase-neutral voltage for the b phase is different:
V
b
n
=
V
a
b
2
−
V
a
n
2
≈
208
V
.
{\displaystyle V_{bn}={\sqrt {{V_{ab}}^{2}-{V_{an}}^{2}}}\approx 208\,{\text{V}}.}
This can be proven by writing a KVL equation, using angle notation, starting from the grounded neutral:
0
+
120
∠
0
∘
+
240
∠
120
∘
=
0
+
120
∠
0
∘
+
240
(
−
0.5
)
∠
0
∘
+
240
3
2
∠
90
∘
=
0
+
120
∠
0
∘
−
120
∠
0
∘
+
240
3
2
∠
90
∘
=
240
3
2
∠
90
∘
=
120
3
∠
90
∘
,
{\displaystyle {\begin{aligned}&0+120\angle 0^{\circ }+240\angle 120^{\circ }\\={}&0+120\angle 0^{\circ }+240(-0.5)\angle 0^{\circ }+240{\frac {\sqrt {3}}{2}}\angle 90^{\circ }\\={}&0+120\angle 0^{\circ }-120\angle 0^{\circ }+240{\frac {\sqrt {3}}{2}}\angle 90^{\circ }\\={}&240{\frac {\sqrt {3}}{2}}\angle 90^{\circ }=120{\sqrt {3}}\angle 90^{\circ },\end{aligned}}}
or:
0
+
120
sin
(
0
∘
)
+
240
sin
(
120
∘
)
=
0
+
0
+
240
3
2
≈
207.8.
{\displaystyle 0+120\sin(0^{\circ })+240\sin(120^{\circ })=0+0+240{\frac {\sqrt {3}}{2}}\approx 207.8.}
Advantages
If the high leg is not used, the system acts like a split single-phase system, which is a common supply configuration in the United States.
Both three-phase and single split-phase power can be supplied from a single transformer bank.
Where the three-phase load is small relative to the total load, two individual transformers may be used instead of the three for a full delta or a three-phase transformer, thus providing a variety of voltages at a reduced cost. This is called open-delta high-leg, and has a reduced capacity relative to a full delta.
Disadvantages
In cases where the single-phase load is much greater than the three-phase load, load balancing will be poor. Generally, these cases are identified by three transformers supplying the service, two of which are sized significantly smaller than the third, and the third larger transformer will be center tap grounded.
One of the phase-to-neutral voltage (usually phase B) is higher than the other two. The hazard of this is that if single phase loads are connected to the high leg (with the connecting person unaware that leg is higher voltage), excess voltage is supplied to that load. This can easily cause failure of the load.
Commonly there is a high-leg to neutral load limit when only two transformers are used. One transformer manufacturer suggests that high-leg-to-neutral loading not exceed 5% of transformer capacity.
Applications
It is often found in older and rural installations. This type of service is usually supplied using 240 V line-to-line and 120 V line-to-neutral. In some ways, the high leg delta service provides the best of both worlds: a line-to-line voltage that is higher than the usual 208 V that most three-phase services have, and a line-to-neutral voltage (on two of the phases) sufficient for connecting appliances and lighting. Thus, large pieces of equipment will draw less current than with 208 V, requiring smaller wire and breaker sizes. Lights and appliances requiring 120 V can be connected to phases A and C without requiring an additional step-down transformer.
It is also commonly used in installations in Japan. The distribution transformer output is 200 V line-to-line and 100 V line-to-neutral, while the high-leg to neutral voltage is 173 V. This provides 200 V for both three-phase and split-phase appliances.
Even when unmarked, it is generally easy to identify this type of system, because the B phase (circuits #3 and #4) and every third circuit afterwards will be either a three-pole breaker or a blank.
Current practice is to give separate services for single-phase and three-phase loads, e.g., 120 V split-phase (lighting etc.) and 240 V to 600 V three-phase (for large motors). However, many jurisdictions forbid more than one class for a premises' service, and the choice may come down to 120/240 V split-phase, 208 V single-phase or three-phase (delta), 120/208 V three-phase (wye), or 277/480 V three-phase (wye) (or 347/600 V three-phase (wye) in Canada).
See also
Transformer
Three-phase electric power
Electric power distribution
Mains electricity
Mains electricity by country
Scott-T transformer
References
= Footnotes
== Works cited
=Kata Kunci Pencarian:
- Hong Kong
- Madonna
- Pit bull
- Daftar lagu rock instrumental
- Use Your Illusion World Tours
- Chinese Democracy Tour
- High-leg delta
- Three-phase electric power
- Delta
- Delta-wye transformer
- Electrical wiring in North America
- Stinger (disambiguation)
- Scott-T transformer
- Electrical code
- IEC 60309
- Transformer types